1.General Introduction

ABB TSP311 temperature transmitter is a heavy duty modular type sensor without thermowell which used for insertion in an existing or separate thermowell, sensor can be replaced during operation, transmitter head can be either integrated or remote mounted, both RTD and thermocouple sensors accepted, sensor meets SIL2 approval when integrated with transmitter. Both TTH200 and TTH300 can be integrated; recommend using an LC display with type AS display function if using a TTH200 and LCD indicator with type A if using TTH300.

2.Compare Table of TSP311 TPS321 and TSP311

Type

TSP311

TSP321

TSP331

Design

No thermowell, for installation in existing thermowell

Welded protective fitting

manufactured from pipe material

Drilled thermowell manufactured

from bar stock material

Measuring inset, extension tube with   thermowell interface, connection head, transmitter, optional LCD display

Process connection

Insertion in an existing thermowell.

 

Screw-in thread, flange,

compression fitting

Welded connections, screw-in

thread, flange

Transport temperature / Storage

temperature

-20 to 70℃ (-4 to 158°F)

Maximum temperature limits

(depending on the sensor and material   selected, the lower temperature value in each case counts)

Sensor

Thin film resistor: 400℃(752°F), wire wound resistor: 800℃ (1472°F),

Thermocouples type K, N, J, E, L, S:   1600℃ (2912°F)

Material

Temperature limits

316L / 1.4404

≤ 800℃ (1472°F)

316Ti / 1.4571

≤ 800℃ (1472°F)

Inconel 600 / 2.4816

≤ 1100℃ (2012°F)

Hastelloy C276 / 2.4819

≤ 1100℃ (2012°F)

≤ 1100℃ (2012°F)

Monel 400 / 2.4360

600℃ (1112°F)

1.7335

≤ 540℃ (1004°F)

1.7380

≤ 570℃ (1058°F)

1.5415

≤ 500℃ (932°F)

E-CTFE

≤ 120℃ (248°F)

≤ 120℃ (248°F)

Tantalum

≤ 250℃ (482°F)

≤ 250℃ (482°F)

Pressure


Maximum 40 ... 100 bar

(580.15 bar ... 1450.38 psi)

Maximum 700 bar (10152.64 psi)

 

3.Basic Code Selection of TSP311 Temperature Transmitter

Main Code

Suffix Codes

Description

TSP311











SensyTemp TSP311 Temperature Sensor, without thermowell, for heavy duty applications

Explosion Protection / Approvals

Y0










Without explosion   protection

A1










Intrinsic Safety ATEX II 1 G Ex ia IIC T6 Ga or II 2 G Ex ib IIC T6 Gb   or II 1/2 G Ex ib IIC T6 Ga/Gb

A3










Dust ignition   proof ATEX II 1 D IP6x

A4










Dust ignition proof ATEX II 1 D IP6x T133 ... T400 and Intrinsic Safety ATEX   II 1 G Ex ia IIC T6 ... T1

A5










Flameproof   enclosure ATEX II 1/2 G Ex d IIC T1 - T6 Ga/Gb

B1










Non incentive ATEX II 3 G Ex nA IIC T1 - T6 Gc and ATEX II 3 D Ex tc   IIIB T133°C Dc

B5










Dust ignition proof ATEX II 1 D IP6x T133 and Flameproof enclosure ATEX   II 1/2 G Ex d IIC T6

H1










Intrinsic Safety IECEx ia IIC T6 Ga

H2










Intrinsic Safety IECEx ib IIC T6 Gb or IECEx ib IIC T6 Ga/Gb

H5










Flameproof   enclosure IECEx d IIC T1 - T6 Ga/Gb

N1










Intrinsic Safety acc. NAMUR NE 24 and ATEX II 1 G Ex ia IIC T6 Ga

G1










GOST Russia -   metrological approval

P2










GOST Russia -   metrological approval and EAC-Ex, Ex i - Zone 0

P3










GOST Russia -   metrological approval and EAC-Ex, Ex d

P4










GOST Russia -   metrological approval and EAC-Ex, dust ignition proof

G3










GOST Kazakhstan   - metrological approval

T2










GOST Kazakhstan   - metrological approval and EAC-Ex, Ex i - Zone 0

T3










GOST Kazakhstan   - metrological approval and EAC-Ex, Ex d

T4










GOST Kazakhstan   - metrological approval and EAC-Ex, dust ignition proof

M5










GOST Belarus -   metrological approval

U2










GOST Belarus -   metrological approval and EAC-Ex, Ex i - Zone 0

U3










GOST Belarus -   metrological approval and EAC-Ex, Ex d

U4










GOST Belarus -   metrological approval and EAC-Ex, dust ignition proof

Extension Tube   Length


Y0









Without Extension   Tube


K1









K = 150 mm (6 inch)


Z9









Customer   specific length

Thermowell   Connection



W1








No extension / Connection head with thread M24x 1.5



W2








No extension / Connection head with thread 1/2 inch NPT



W3








No extension / Connection head with lock nut M24x 1.5



W4








Double nipple / G 1/2 A / G 1/2 A



W5








Double nipple / 1/2 in. NPT / 1/2 in. NPT



G1








Extension tube with Cylindrical thread G 1/2 A



G2








Extension tube with Cylindrical thread G 3/4 A



G3








Extension tube with Cylindrical thread G 3/8 A



M1








Extension tube with Cylindrical thread M14x1.5



M2








Extension tube with Cylindrical thread M18x1.5



M3








Extension tube with Cylindrical thread M20x1.5



M4








Extension tube with Cylindrical thread M24x1.5



M5








Extension tube with Cylindrical thread M27x1.5



N1








Extension tube with conical thread 1/2 in. NPT



N2








Nipple / 1/2 in. NPT / 1/2 in. NPT



N3








Nipple-Union / 1/2 in. NPT / Union 1/2 in. NPT



N4








Nipple - Union - Nipple / 1/2 in. NPT / 1/2 in. NPT



U6








Extension with Male nut, thread G 1/2 in.



A1








Extension tube with adjustable compression fitting G 1/2 A



A2








Extension tube with adjustable compression fitting 1/2 in. NPT



Z9








Others

Immersion Length




U2







U = 140 mm (5.6   in.)




U4







U = 200 mm (8   in.)




U6







U = 260 mm (10.3   in.)




Z9







Customer   specific length

Measuring Inset Type





S1






RTD, TF, Basic   application, measuring range -50 ... 400℃ (-58 ... 752°F),   10 g





S2






RTD, TF, Extended   vibration resistance, measuring range -50 ... 400℃ (-58 ... 752°F),   60 g





S3






RTD, TF, Extended   measuring range -196 ... 400℃ (-321 ... 752°F), 10 g





S4






RTD, TF, Extended   vibration resistance, extended measuring range -196 ... 400℃ (-321 ... 752°F),   60 g





D1






RTD, WW, Extended   measuring range -196 ... 600℃ (-321 ... 1112°F), 10 g





D3






RTD, WW, Extended   vibration resistance, extended measuring range -196 ... 600℃ (-321 ... 1112°F),   60 g





E1






RTD, adjustable   to German calibration regulations, sign of app. 000/308 - without calibration





E2






RTD, custody   preliminary, adjustable to German regulations, - with calibration -10℃ and   +50℃





T1






Thermocouple





Z9






Others

Measuring Inset Diameter






D3





3 mm






D4





4.5 mm






D6





6 mm






D8





8 mm






H8





8 mm, tip with   sleeve, DIN 43735 Sleeve 80 mm (RTD), 20 mm (TC)






H1





10 mm, tip with   sleeve 80 mm (RTD), 20 mm (TC)






Z9





Others

Sensor Type and Wiring







P1




1 x Pt100,   2-wire







P2




1 x Pt100,   3-wire







P3




1 x Pt100,   4-wire







P4




2 x Pt100,   2-wire







P5




2 x Pt100,   3-wire







P6




2 x Pt100,   4-wire







P8




1 x Pt1000,   2-wire







P7




1 x Pt1000,   3-wire







P9




1 x Pt1000,   4-wire







K1




1 x Type K   (NiCr-NiAl)







K2




2 x Type K   (NiCr-NiAl)







K3




3 x Type K   (NiCr-NiAl)







J1




1 x Type J   (Fe-CuNi)







J2




2 x Type J   (Fe-CuNi)







L1




1 x Type L   (Fe-CuNi)







L2




2 x Type L   (Fe-CuNi)







N1




1 x Type N   (NiCrSi-NiSi)







N2




2 x Type N   (NiCrSi-NiSi)







T1




1 x Type T   (Cu-CuNi)







T2




2 x Type T   (Cu-CuNi)







E1




1 x Type E   (NiCr-CuNi)







E2




2 x Type E   (NiCr-CuNi)







S1




1 x Type S   (Pt10Rh-Pt)







S2




2 x Type S   (Pt10Rh-Pt)







Z9




Others

Sensor Accuracy








B2



Accuracy Class   B, IEC 60751








D2



Wire Wound,   Double, Accuracy Class A, IEC 60751, Range 0 ... 250℃ (32 ... 482°F)








D1



Wire Wound,   Accuracy Class A, IEC 60751, Range -100 ... 450℃ (-148 ... 842°F)








S1



Thin Film,   Accuracy Class A, IEC 60751, Range -30 ... 300℃ (-22 ... 572°F)








S3



Thin Film,   Accuracy Class AA, IEC 60751, Range 0 ... 100℃ (0 ... 212°F)








S6



Thin Film,   Accuracy Class A extended according to IEC 60751, Range -196 ... 400℃ (-320,8 ... 752°F)








S8



Thin Film,   Accuracy Class AA extended according to IEC 60751, Range -196 ... 400℃   (-320,8 ... 752°F)








T2



Thermocouple,   Accuracy Class 2, IEC 60584








T1



Thermocouple,   Accuracy Class 1, IEC 60584








T4



Thermocouple, Standard   Accuracy ANSI MC96.1








T3



Thermocouple,   Special Accuracy ANSI MC96.1








T5



Thermocouple,   Accuracy according to DIN 43710








Z9



Others

Connection Head Type / Material









L1


AGL / Aluminium,   screwed cover









L2


AGLH /   Aluminium, high cover, screwed









L4


AGLD /   Aluminium, screwed cover with display









S1


AGS / Stainless   steel, screwed cover









S2


AGSH / Stainless   steel, high cover, screwed









S4


AGSD / Stainless   steel, screwed cover with display









Z9


Others

Transmitter










Y1

Without   transmitter, sensor with ceramic terminal block - spring loaded










Y2

Without   transmitter, sensor with flying leads and metal plate - spring loaded










H4

TTH300-HART,   programmable, output signal 4 ... 20mA, dual input










H5

TTH300-HART, Ex   version, programmable, output signal 4 ... 20mA, dual input










P6

TTH300-PA,   programmable, output PROFIBUS PA, dual input










P7

TTH300-PA, Ex   version, programmable, output PROFIBUS PA, dual input










F6

TTH300-FF,   programmable, output FOUNDATION fieldbus H1, dual input










F7

TTH300-FF, Ex   version, programmable, output FOUNDATION fieldbus H1, dual input










H6

TTH200-HART,   programmable, output signal 4 ... 20mA










H7

TTH200-HART, Ex   version, programmable, output signal 4 ... 20mA

Optional Codes

/Optional codes